Quick Tips

OSHA Code of Federal Regulations
• Requires adequate and reliable illumination for all exits
• Requires proper maintenance to assure that exit lighting is in continuously proper operating condition
NFPA 70 - National Electric Code
• Requires specific illumination and performance of emergency and exit lights
• Provides functional standards for battery-powered emergency and exit lighting
NFPA 101 - Life Safety Code
• Requires a monthly inspection of all emergency and exit lighting systems
• Requires an annual test of all emergency and exit lighint systems
International Fire Code
• Requires proper illumination of means of egress
• Requires assurance that emergency and exit lighting systems will provide illumination for at least 60 minutes
NFPA 1997 5-9.3
Periodic Testing of Emergency Lighting Equipment
An annual test shall be conducted for a 1-1/2 hour duration. Equipment shall be fully functional for the duration of the test.
Standard Fire Prevention Code 1999
807.1.4 Exit Illumination and Signs A functional test shall be conducted on every required emergency lighting system at 30-day intervals for a minimum of 30-seconds.

Emergency Lights

Series LGSHL High Lumen Indoor Emergency Light

Product Code: LGSHL

Steel Housing 12V up to 40W Capacities High-Performance LED Emergency Lighting Unit

Standard LED Emergency Light Series : ELLE

Product Code: ELLE

White or Black Housing

Adjustable Optics LED Emergency Light Series : ELRTL

Product Code: ELRTL

Adjustable Optics LED Emergency Light Series : ELRTL

Decorative Halogen or LED MR16 Emergency Light

Product Code: EL16

Decorative Halogen or LED MR16 Emergency Light available in White or Black Housing

Decorative High-Capacity Emergency Light with 9-hour Runtime Series: ELMR50

Product Code: ELMR50

Decorative High-Capacity Emergency Light with 9-hour Runtime Series: ELMR50

Remote Capable MR-16 Emergency Light Series : ELR16HO

Product Code: ELR16HO

Decorative Indoor MR16 Emergency Light with Remote Head Capacity | Series ELR16HO

Semi-Recessed MR-16 Emergency Light Series : ELMR16L

Product Code: ELMR16L

Semi-Recessed MR-16 Emergency Light Series : ELMR16L

Remote Capable LED Emergency Light Series : ELRFH

Product Code: ELRFH

Remote Capable LED Emergency Light Series : ELRFH

LED Low Profile Thermoplastic Emergency Light Series : ELEO

Product Code: ELEO

LED Low Profile Thermoplastic Emergency Light Series : ELEO

Fixed-Optics Incandescent Emergency Light Series : ELR2

Product Code: ELR2

White or Black Housing

Wet Location Semi-Recessed MR-16 Emergency Light Series  : ELMR16WP

Product Code: ELMR16WP

Clear housing design looks great

Glare-Free PAR-Type Emergency Light Series : ELNYXR

Product Code: ELNYXR

Glare-Free PAR-Type Emergency Light Series : ELNYXR

Thermoplastic Emergency Light Series : ELEC

Product Code: ELEC

Thermoplastic Emergency Light Series : ELEC

Chicago Approved Steel LED Emergency Light Series :ELCALR

Product Code: ELCALR

Chicago Approved Steel LED Emergency Light Series :ELCALR

Adjustable Recessed Emergency Down-light Series : EMRL

Product Code: EMRL

EMRL

Halogen Emergency Light Series : ELCA

Product Code: ELCA

Halogen Emergency Light Series : ELCA

Wet Location Remote Capable LED Emergency Light Series : ELTX

Product Code: ELTX

Wet Location Remote Capable LED Emergency Light Series : ELTX

Incandescent Emergency Light Series : ELR7

Product Code: ELR7

Incandescent Emergency Light Series : ELR7

Fully Recessed Emergency Light Series : ELSE

Product Code: ELSE

Fully Recessed Emergency Light Series : ELSE

Wet-Location Incandescent Emergency Light Series : ELTFX2

Product Code: ELTFX2

Wet-Location Incandescent Emergency Light Series : ELTFX2

Remote Capable Incandescent Emergency Light Series : ELXR

Product Code: ELXR

White or Black Housing

6 and 12 Volt Steel Enclosure Emergency Light Series : EL89

Product Code: EL89

6 and 12 Volt Steel Enclosure Emergency Light Series : EL89

Steel Housing LED Emergency Light Series : ELSDXLR627

Product Code: ELSDXLR627

Steel Housing LED Emergency Light Series : ELSDXLR627

Decorative Outdoor LED Emergency Light Series : ELBO

Product Code: ELBO

LED Decorative Outdoor Die-Cast AC/Emergency Unit Series : ELBO

Incandescent Emergency Light Series : ELTB

Product Code: ELTB

Incandescent Emergency Light Series : ELTB

High Impact Enclosure Power Unit Emergency Light Series : ELKS

Product Code: ELKS

High Impact Enclosure Power Unit Emergency Light Series : ELKS

Cold Storage NEMA-4X and NSF rated Industrial Emergency Lighting Unit Series: ELV18M

Product Code: ELV18M

Ideal for cold storage and food prep applications, the NEMA-4X and NSF Certified ELV18M Series delivers reliable, energy efficient, Emergency Lighting

Die-Cast Aluminum LED Emergency Light Series : ELUX

Product Code: ELUX

Die-Cast Aluminum LED Emergency Light Series : ELUX

Decorative Industrial Emergency Light Series : ELIDE

Product Code: ELIDE

Decorative Industrial Emergency Light Series : ELIDE

Industrial High Capacity Emergency Light Series : ELIHC

Product Code: ELIHC

Industrial High Capacity Emergency Light Series : ELIHC

5-8.1.3* The floors of means of egress shall be illuminated at all points including angles and intersections of corridors and passageways, stairways, landings of stairs, and exit doors to values of not less than 1 footcandle (10 lx) measured at the floor. Exception: In assembly occupancies, the illumination of the floors of exit access shall be not less than 1/5 footcandle (2 lx) during periods of performances or projections involving directed light.

5-9.2.1*
 Emergency illumination shall be provided for a period of 1 1/2 hours in the event of failure of normal Lighting. Emergency Lighting facilities shall be arranged to provide initial illumination that is no less than an average of 1 footcandle (10 lx) and a minimum at any point of .1 footcandle (1 lx) measured along the path of egress at floor level. Illumination levels may decline to .6 footcandle (6 lx) average and a minimum at any point of .06 footcandle (.6 lx) at the end of the emergency Lighting time duration. A maximum to minimum illumination uniformity ratio of 40 to 1 shall not be exceeded.




Protecting Those Who Serve